A 24 VDC two-wire circuit carries a lumped 1.20 A load at its end. The one-way length is 250 ft and each conductor has 2.525 Ω/1,000 ft resistance. Ignoring other losses, what voltage reaches the load?
- 23.24 V
- 20.97 V
- 21.00 V
- 22.49 V
Strengthen field judgment. Documentation, troubleshooting, circuit loads, and system interfaces.
Scenario-based Fire Alarm Systems practice. Four plausible choices per question. Not official NICET exam content.
Enable JavaScript for answer selection, scoring, and explanations.
Use this Level 2 (Level II) practice sample to check your reasoning on the topics below. These are sample review topics, not a complete official exam outline.
Keep amps, milliamps, hours, minutes, feet, and ohms consistent. Many plausible wrong answers come from using one-way conductor length, failing to convert alarm minutes, or omitting an auxiliary load.
A circuit that operates on primary power still needs evaluation under required secondary-power conditions. Distinguish nominal voltage from the documented voltage available to the circuit during the condition being checked.
A corridor layout must satisfy both end offsets and device separation under its applicable reference. Meeting one constraint does not establish the other. Room and corridor methods are separate decisions.
For a complete preparation plan, compare your review with NICET’s official Level II content outline. Use the references permitted for your scheduled exam.
Documentation, troubleshooting, circuit loads, and system interfaces. Use each missed question to choose a subject for deeper review in your references. These scenarios include field judgment and calculation review; a short sample cannot assess certification readiness.
In the app, explore Levels I–IV, quick exams, timed practice, missed-question review, and progress tracking. Certification includes requirements beyond examination performance.
Official NICET program information · Check current exam references